How to choose between an analog current loop, Modbus RTU over RS485, and a combined transmitter requirement before requesting a pressure-instrument quote.

Reviewed November 12, 2026Editorial procurement frameworkExact-model confirmation required
01

Begin with the receiver, not the sensor

The output should match the device that will receive the measurement. Identify the PLC, controller, panel meter, data logger or supervisory system; its available input channels; the required scan rate; and who will own scaling, alarms and diagnostics.

A pressure transmitter can measure the same pressure with several electrical interfaces, but the wiring, commissioning and system architecture are different. Write down those constraints before comparing model numbers.

02

Choose 4–20 mA for a direct analog loop

A 4–20 mA output is a point-to-point analog signal commonly used where a PLC or controller has a current-input channel. It is straightforward to scale and can be configured as a current loop when the controller, supply and transmitter are compatible.

Confirm loop supply, transmitter burden, cable length, voltage drop, grounding, isolation and whether the output is two-wire or three-wire. Do not assume that a product described as 4–20 mA is HART-capable; HART is an additional communication layer that must be specified explicitly.

03

Choose RS485 when the system needs a digital fieldbus

RS485 is a physical layer and does not by itself define a usable protocol. Pressure instruments commonly use Modbus RTU, so confirm the protocol, baud rate, parity, device address, register map, word order and support for the controller's polling software.

RS485 is often useful for multi-drop installations, but the shared bus needs correct topology, termination, biasing and cable routing. Verify maximum devices, cable length, isolation and failure behaviour before assuming that adding another transmitter is plug-and-play.

04

Decide whether you need analog and digital together

Some transmitters offer a 4–20 mA signal and a digital interface; others offer them as alternatives. Ask whether both outputs are simultaneous, which settings are independent, and whether configuration requires proprietary software.

If the process needs a local display, switch output, relays, min/max logging or hazardous-area approval, include those requirements explicitly. They may affect the electronics, enclosure and available output combinations.

  • State the controller model and the exact input or protocol it supports.
  • Confirm whether the transmitter must be two-wire, three-wire or four-wire.
  • Provide the register map or output scaling expected by the receiving system.
  • Require a test or configuration record before shipment.
05

Keep the pressure and mechanical specification separate

The electrical choice does not replace the pressure basis. Confirm gauge, absolute, differential or sealed-gauge measurement; normal and maximum pressure; proof pressure; process temperature; wetted materials; thread or flange; and the required accuracy basis.

The RFQ should give the desired accuracy and the reference conditions used to compare it. If the supplier changes the accuracy definition, range basis or temperature-compensation statement, document that change in the quotation.